技術文章您的位置:網站首頁 >技術文章 >恒溫恒濕試驗箱保護注意事項和方法

恒溫恒濕試驗箱保護注意事項和方法

更新時間:2016-06-29   點擊次數:2029次

恒(heng)(heng)溫(wen)恒(heng)(heng)濕(shi)試(shi)(shi)驗(yan)箱也稱恒(heng)(heng)溫(wen)恒(heng)(heng)濕(shi)試(shi)(shi)驗(yan)機、恒(heng)(heng)溫(wen)恒(heng)(heng)濕(shi)試(shi)(shi)驗(yan)箱或恒(heng)(heng)溫(wen)機或恒(heng)(heng)溫(wen)恒(heng)(heng)濕(shi)箱,用(yong)于檢測材料在各(ge)種環(huan)境(jing)(jing)下功(gong)用(yong)的(de)設(she)備及試(shi)(shi)驗(yan)各(ge)種材料耐(nai)(nai)熱(re)耐(nai)(nai)寒耐(nai)(nai)干(gan)以及耐(nai)(nai)濕(shi)功(gong)用(yong)。適(shi)宜電(dian)子、電(dian)器、通訊、表面、車輛、塑膠制品(pin)、金屬、食物、化學、建材以及醫療(liao)等制品(pin)檢測質量(liang)之(zhi)用(yong)。恒(heng)(heng)溫(wen)恒(heng)(heng)濕(shi)試(shi)(shi)驗(yan)箱是調集(ji)了(le)高溫(wen)文低(di)溫(wen)以及濕(shi)熱(re)為(wei)一體的(de)試(shi)(shi)驗(yan)箱高低(di)溫(wen)濕(shi)熱(re)交變試(shi)(shi)驗(yan)箱,它的(de)修補難度較其它環(huan)境(jing)(jing)試(shi)(shi)驗(yan)設(she)備大,且具有代表性(xing)。下面談(tan)一談(tan)恒(heng)(heng)溫(wen)恒(heng)(heng)濕(shi)試(shi)(shi)驗(yan)箱保護注意(yi)事(shi)項和方法。

  1.冷(leng)凍(dong)機(ji)(ji)組(zu)之散熱(冷(leng)凝器(qi))應守(shou)時(shi)保護,堅(jian)持(chi)清洗。塵(chen)(chen)土粘糊冷(leng)凝器(qi)會使壓縮機(ji)(ji)高壓開(kai)關跳脫而發生(sheng)誤報警,冷(leng)凝器(qi)應守(shou)時(shi)每月保護,運用真空(kong)吸塵(chen)(chen)器(qi)將(jiang)冷(leng)凝器(qi)散熱網片上附著之塵(chen)(chen)土吸除或開(kai)機(ji)(ji)后運用質(zhi)硬的毛刷(shua)刷(shua)之或用高壓氣嘴(zui)吹(chui)潔凈塵(chen)(chen)土。

  2.開(kai)關門(men)或從(cong)爐內取檢驗物時,不得讓物品號門(men)上(shang)膠邊接觸,以防膠邊被損壞和縮短壽數。

  3.機身(shen)周圍(wei)和底(di)部的(de)地上要隨時堅持(chi)清洗,防止很多(duo)塵土吸入(ru)機組內(nei)發生意外事故和下(xia)降(jiang)功用。

  4.冷凍系統(tong)是本機的中間,請一(yi)年巡檢(jian)一(yi)次全(quan)部銅管有(you)無走(zou)漏雪種(zhong)情況,各喇(la)叭(ba)接(jie)頭、焊接(jie)口,如(ru)有(you)油污外(wai)泄,請通知本公司(si)或(huo)直接(jie)處置之。

  5.配電盤之大電流接(jie)點配電室(shi)(shi)內(nei)每年至少清洗檢(jian)修(xiu)一次以上,接(jie)點的松動會使(shi)整個設備處于危險工作情況,輕則(ze)燒壞組(zu)件,重則(ze)發生火災(zai)、報警、人身損(sun)害十分(fen)危險,清洗時(shi)請(qing)運(yun)用吸(xi)塵器將室(shi)(shi)內(nei)塵土吸(xi)除即可(ke)。

  6.加(jia)濕器及水(shui)銹常常清洗,防止發生水(shui)垢,影響蒸氣的宣布,一般做完一次(ci)實驗清洗一次(ci),水(shui)垢得到及時打掃有利(li)加(jia)濕管的壽數,確(que)保水(shui)流順暢(chang)清洗時運用(yong)銅質刷子(zi)洗刷用(yong)水(shui)沖之潔凈。

  7.干濕球(qiu)之濕布(bu)常常檢查,當檢驗布(bu)表面(mian)不潔凈或變硬,或于高溫85以上控(kong)制后,繼續做溫(wen)(wen)濕度控(kong)制前(qian)。經檢查(cha)如有不吸水者請更(geng)換(huan)(huan)之這關系(xi)到測(ce)濕的準(zhun)確度,檢驗布(bu)一般(ban)三月更(geng)換(huan)(huan)一次,更(geng)換(huan)(huan)時運用清洗(xi)(xi)布(bu)擦拭測(ce)溫(wen)(wen)體(ti),更(geng)換(huan)(huan)新檢驗布(bu)時應先洗(xi)(xi)手再(zai)把水槽清洗(xi)(xi)潔凈。

  8.濕球(qiu)水(shui)(shui)位(wei)之(zhi)(zhi)檢查(cha)與調整(zheng)(zheng):積(ji)(ji)水(shui)(shui)筒(tong)水(shui)(shui)位(wei)不(bu)可過(guo)高由(you)于過(guo)高使水(shui)(shui)溢出積(ji)(ji)水(shui)(shui)筒(tong)或(huo)過(guo)低(di)使濕球(qiu)檢驗布吸水(shui)(shui)不(bu)正常影響濕球(qiu)的(de)準確(que)性。水(shui)(shui)位(wei)大約(yue)堅持六分滿即(ji)可等積(ji)(ji)水(shui)(shui)筒(tong)水(shui)(shui)位(wei)之(zhi)(zhi)調整(zheng)(zheng)就可調整(zheng)(zheng)積(ji)(ji)水(shui)(shui)盒(he)的(de)高低(di)【調整(zheng)(zheng)兩頭螺絲(si)】

  9.配電箱內的超溫保(bao)護(hu)(hu)器設定值請不要(yao)隨意調試(shi),出廠時已調好,此保(bao)護(hu)(hu)開關是保(bao)護(hu)(hu)加熱管和(he)加濕(shi)管空焚和(he)缺水警報之(zhi)用,設定點

  10.試(shi)驗(yan)箱內之溫(wen)(wen)度升至超(chao)(chao)溫(wen)(wen)保護(hu)器(qi)之設定點時加熱器(qi)之供電(dian)(dian)即間斷,超(chao)(chao)溫(wen)(wen)警示燈點亮但電(dian)(dian)扇仍工作(zuo)(zuo),若(ruo)長時間工作(zuo)(zuo)及無人看守,工作(zuo)(zuo)前請勿(wu)必確實檢(jian)查超(chao)(chao)溫(wen)(wen)保護(hu)器(qi),是(shi)(shi)不是(shi)(shi)設定穩妥。

  11.試(shi)驗箱水(shui)(shui)路之(zhi)(zhi)(zhi)檢查(cha)與保護水(shui)(shui)路之(zhi)(zhi)(zhi)水(shui)(shui)管,是易(yi)(yi)堵易(yi)(yi)漏(lou)之(zhi)(zhi)(zhi)器(qi)件(jian),請(qing)有必要守時檢查(cha)有無漏(lou)水(shui)(shui)堵水(shui)(shui)之(zhi)(zhi)(zhi)表(biao)象,若有請(qing)及時打掃或通知本公司。加(jia)濕器(qi)內之(zhi)(zhi)(zhi)儲水(shui)(shui)應每月(yue)更換一次(ci),確保水(shui)(shui)質清洗,水(shui)(shui)流順(shun)暢(chang)。

  12.當試(shi)驗(yan)箱實驗(yan)產品(pin)時(shi)間抵達后取產品(pin)時(shi),有必要(yao)在(zai)關機(ji)情況下且工作人員一定要(yao)戴好(hao)單調、防(fang)電、耐濕手套(tao)進行取放(fang)產品(pin)。

  13.試(shi)驗(yan)(yan)箱體(ti)內(nei)外部的(de)清(qing)洗(xi)與保護機(ji)器(qi)在操作前應先將內(nei)部雜質(zhi)(物(wu))*。配電室內(nei)每(mei)年(nian)至少清(qing)洗(xi)一次以(yi)上清(qing)洗(xi)時請運用吸(xi)塵器(qi)將室內(nei)塵土吸(xi)除即可。試(shi)驗(yan)(yan)箱體(ti)外部每(mei)年(nian)有必(bi)要清(qing)洗(xi)一次以(yi)上,清(qing)洗(xi)時用肥皂水擦拭(shi)即可。